When choosing an alternator, the first question almost everyone asks is: how many kW do I need? It's a natural question, because kW is the unit we use to measure the actual power a load absorbs to function. The problem is that this question, on its own, is not enough. To correctly size an alternator, you need to look at another number, just as important: the power factor, indicated as cos φ.
In this article we try to explain, in simple terms, what this parameter really means and why ignoring it almost always leads to a sizing error, with concrete consequences for the reliability of the system.
Active power and apparent power: two different quantities
In an AC electrical system there are two quantities that are useful to distinguish clearly.
Active power, measured in kW, is the power that is actually converted into useful work: the heat of a resistor, the movement of a motor, the light of a lamp.
Apparent power, measured in kVA, is instead what the alternator must be able to supply to power the load, also taking into account the reactive component required by motors, transformers, UPS units and many modern electronic devices.
The ratio between these two quantities is precisely the power factor:
cos φ = kW / kVA
A power factor of 1 means that all the apparent power is converted into active power, a condition that in practice never occurs with real loads. A power factor of 0.8, a very common value in technical specifications, means that the alternator must supply 25% more apparent power than the active power alone required by the load.
Why this affects the choice of alternator
By design, an alternator has a limit expressed in kVA: this is the value that defines its size, not the kW. If the designer sizes the generating set based only on the required active power, there is a risk of undersizing the machine, because the additional current needed to sustain the reactive component of the load is not taken into account.
Let's take a simple example, without specific product figures, just to clarify the principle: a load requiring 100 kW with a power factor of 0.8 actually needs a 125 kVA alternator, not a 100 kVA one. The difference, in this case 25 kVA, is the reactive power that the machine must still be able to deliver, even though it does not translate into useful work for the end user.
Which loads lower the power factor
Not all loads behave in the same way. Some types of loads, very common in industrial plants and data centers, tend to have a lower power factor than a purely resistive load:
In the presence of these loads, a power factor of 0.8 is a prudent assumption but far from extreme: in some installations with a strong presence of electronic loads, even lower values can be found, which is why the load's technical data sheet, when available, should always be checked before choosing the alternator.
What happens if the sizing is wrong
An alternator undersized relative to the actual apparent power required is unable to sustain the load under the expected conditions. The most frequent consequences are excessive heating of the windings, unstable voltage regulation under load and, in the most critical cases, protection tripping with a resulting service interruption.
Conversely, an alternator oversized out of excessive caution results in a higher initial investment, larger dimensions and, in many operating conditions, suboptimal efficiency, because the machine works far from its ideal operating point.
Correct sizing, therefore, is not a minor technical detail: it is the foundation on which the reliability of the entire system is built.
How to proceed in practice
For those who need to specify an alternator, the advice is to follow a simple but rigorous path:
Choosing an alternator by looking only at kW is a common but avoidable mistake. The load's power factor determines how much apparent power, and therefore how much current, the alternator must actually be able to sustain. Knowing this principle, simple but often overlooked, is the first step to avoiding surprises during operation and to building a reliable system over time, as has always been the case for those who design this type of machine with attention to the fundamentals of electrical engineering.